RESIDENTIAL TENANCY (SMOKE ALARMS) REGULATIONS 2022 - REG 13
Placement of smoke alarms where compliance with this Part impracticable
If a smoke alarm cannot be installed on or near the ceiling
because
(a) the structure of the part of the premises in which the smoke alarm is to
be installed does not permit the smoke alarm to be placed on or near the
ceiling of the part of the premises; or
(b) the placement of the smoke alarm on the ceiling is likely to result in the
smoke alarm emitting a warning of the presence of smoke in circumstances where
the smoke does not emanate from a fire that is unattended by a person; or
(c) in the case of a cathedral ceiling, a dead air space will trap air and
thereby prevent smoke from reaching a smoke alarm
the smoke alarm
may be installed on an interior side wall if
(d) the smoke alarm is suitable for such application; and
(e) the top of the smoke alarm is located between 300mm and 500mm from the
ceiling; and
(f) in the case of a cathedral ceiling, the distance from the apex of the
cathedral ceiling to the top of the smoke alarm is between 500mm and
1 500mm.